Free HVAC study guide · 6-9 min read

HVAC Airflow, Static Pressure & Delta T Study Guide

Delta T, CFM, static pressure, duct basics, psychrometrics and filters: the airflow knowledge HVAC technicians are tested on.

A refresher for people already in the trade, not a training course. Always follow the equipment manufacturer’s instructions and current codes.

Lesson 1 of 8

Delta T Measurement

Understanding Delta T (Temperature Difference)

Cooling ΔT
Return - Supply
Target: 16-22°F
Heating ΔT
Supply - Return
Target: 30-50°F

Low ΔT = Possible low airflow, dirty filter, or refrigerant issue
High ΔT = Possible restricted airflow or oversized system

Check yourself: What is the target cooling Delta T range?
  1. 10-15°F
  2. 16-22°F
  3. 25-30°F
  4. 30-50°F

Answer: B. 16-22°F

Lesson 2 of 8

CFM & Static Pressure

Airflow Measurement

CFM (Cubic Feet per Minute):

  • Cooling: 400 CFM per ton
  • Heating: varies by furnace BTU and rise

Static Pressure:

  • Total external static pressure: 0.5" WC max
  • Measure with manometer or magnehelic gauge
  • Supply + Return = Total ESP
Check yourself: What is the recommended CFM per ton for cooling?
  1. 200
  2. 300
  3. 400
  4. 500

Answer: C. 400

Lesson 3 of 8

Duct Design Basics

Sizing Ductwork Correctly

  • Ducts are sized using a friction rate and a duct slide rule or software (like Manual D), based on required CFM.
  • Undersized trunk or branch ducts create excess static pressure and reduce delivered airflow.
  • Flex duct should be pulled tight — sagging or coiled flex duct dramatically increases resistance.
  • Return air must be sized generously; undersized returns are one of the most common airflow problems in the field.
Check yourself: What is one of the most common airflow problems found in the field?
  1. Oversized return ductwork
  2. Undersized return ductwork
  3. Too much insulation on supply ducts
  4. Excess refrigerant charge

Answer: B. Undersized return ductwork

Lesson 4 of 8

Diagnosing Airflow Problems

Symptoms and Root Causes

SymptomLikely Cause
Frozen evaporator coilDirty filter, closed dampers, undersized return, low charge
High static pressureDirty coil/filter, undersized ducts, closed dampers
Weak airflow at one registerCrushed/kinked duct, closed damper, disconnected duct
Noisy operationOversized blower speed for the duct system, loose panels
Check yourself: A frozen evaporator coil is most often linked to what root cause?
  1. Excess airflow
  2. Low airflow across the coil
  3. Overcharged system only
  4. High outdoor temperature

Answer: B. Low airflow across the coil

Lesson 5 of 8

Psychrometrics & Humidity

Sensible Heat, Latent Heat, and Moisture

  • Sensible heat: heat that changes a substance's temperature (what a thermometer reads), with no change in physical state.
  • Latent heat: the heat required to convert a liquid into vapor, without change of temperature (and, in reverse, the heat released when a vapor condenses back into a liquid). In an HVAC system this shows up as the heat absorbed when water vapor in the air condenses into liquid on the cold evaporator coil — the water changes state and releases its latent heat into the coil, which is how moisture is removed from the air. Because temperature doesn't change during this process, latent heat doesn't register on a thermometer, even though real heat energy is being moved.
  • Total cooling capacity is the sum of sensible heat removal (temperature drop) and latent heat removal (dehumidification) — a system's sensible-to-total ratio describes how that capacity splits between the two.
  • Dew point: the temperature at which air becomes saturated and moisture begins to condense.
  • Slower airflow across the evaporator coil increases dehumidification (more contact time for latent heat transfer) but reduces sensible cooling capacity.
Check yourself: As moisture condenses on a cold evaporator coil, which type of heat is being removed from the air - with no change in temperature?
  1. Sensible heat
  2. Latent heat
  3. Radiant heat
  4. Specific heat

Answer: B. Latent heat

Lesson 6 of 8

Zoning & System Balancing

Balancing Airflow Across a System

  • Balancing dampers at each branch allow airflow to be adjusted room by room without changing blower speed.
  • Zoning systems use motorized dampers and a bypass or variable-speed blower to serve different areas independently.
  • Always balance a system with all registers open and filters clean — balancing a dirty system just bakes in the wrong numbers.
Check yourself: What should be true about a system before you balance its airflow?
  1. Filters should be dirty to simulate real conditions
  2. Registers should be partially closed
  3. Filters should be clean and registers open
  4. The blower should be off

Answer: C. Filters should be clean and registers open

Lesson 7 of 8

Filter Types & MERV Ratings

Choosing the Right Filter

  • MERV (Minimum Efficiency Reporting Value) rates how well a filter captures particles - higher MERV means finer filtration.
  • MERV 8-11 is typical for residential systems - a good balance of filtration and airflow.
  • MERV 13+ filters capture much finer particles but add significant static pressure - verify the blower and duct system can handle it before upgrading.
  • A filter that's "too good" for the system can starve airflow just as badly as a dirty one.
Field tip: Always check manufacturer specs before recommending a higher-MERV filter upgrade - not every system is designed to handle the added resistance.
Check yourself: What is a risk of installing too high a MERV-rated filter without checking the system?
  1. It will not fit the filter slot
  2. It can restrict airflow beyond what the blower and ducts were designed for
  3. It will lower the SEER rating
  4. It has no real downside

Answer: B. It can restrict airflow beyond what the blower and ducts were designed for

Lesson 8 of 8

Ventilation & Fresh Air Requirements

Bringing Outside Air Into the System

  • Modern tightly-sealed homes and commercial buildings often need mechanical ventilation to maintain healthy indoor air quality.
  • ERV (Energy Recovery Ventilator): exchanges heat and humidity between incoming and outgoing air streams - good for humid climates.
  • HRV (Heat Recovery Ventilator): exchanges heat only, without transferring humidity - better suited to drier climates.
  • Ventilation airflow is balanced separately from the conditioning system's airflow, but both interact with total static pressure and must be considered together.
Check yourself: Which ventilation device transfers both heat and humidity between air streams?
  1. HRV
  2. ERV
  3. TXV
  4. EEV

Answer: B. ERV